Texas Energy Data

What Commercial Energy Really Costs in Texas

Texas has some of the cheapest electricity rates in the country, so why does your commercial power bill hurt so much? Because the rate you shop for is not the cost you pay. Here is what is actually on the bill, and the one line item that controls half of it.

Kahn Mechanical Contractors 10 min read Updated 2026
~9¢/kWhTexas commercial energy rate, about 35% below the U.S. average
30-50%Of a commercial bill that demand charges alone can reach
~39%Of a building's energy use that HVAC is responsible for

If you have ever compared electricity plans, you know the game is won or lost on the price per kilowatt-hour. Shop hard, lock in a good rate, done. Except for a commercial building, that number is only a slice of the bill, and the parts you did not shop for are often the parts that hurt.

Here is the setup. Texas runs a deregulated market with more than a hundred retail providers competing on price, which pushes commercial energy rates down to roughly 7 to 9.5 cents per kilowatt-hour, among the lowest in the nation. Yet business owners across Dallas-Fort Worth still open their bills and wince. The reason is that the advertised energy rate is only one of several layers, and for many buildings it is not even the biggest one.

Anatomy of a commercial power bill
Your Bill 4 layers
Energy charges 45 to 55%The per-kWh cost you actually shop for. The only fully negotiable layer.
Delivery charges 35 to 45%Your utility's regulated fee for poles, wires, and meters. In DFW that is Oncor. Non-negotiable, same for everyone.
Demand charges up to 30 to 50%Based on your single highest power spike, not total usage. The layer almost nobody understands.
Taxes & riders 3 to 5%Transmission recovery, ancillary services, and state and local taxes.

Typical composition. For buildings with spiky loads, demand charges swell and can rival or exceed the energy charge itself.

Switching providers only touches the yellow slice. The rest arrives no matter who supplies your power. So if you want to actually lower the bill, you have to look at the slice most owners have never even heard of.

The Hidden Driver

The Line Item That Controls Half Your Bill

Demand charges are the reason two businesses can use the exact same total electricity in a month and pay wildly different bills. A demand charge is not based on how much power you use. It is based on the single highest 15-minute burst of power you draw all month.

Your utility installs an interval meter that records your draw every 15 minutes. At the end of the billing cycle, it finds your worst 15 minutes, converts that to kilowatts, and multiplies it by a per-kW rate. In Oncor territory across DFW, that rate runs about $14 per kW. That one peak sets a charge that applies to the entire month, no matter how efficiently you ran the other 2,975 intervals.

The lunch-rush problem

Picture a restaurant. During one Friday lunch, the convection ovens fire, the exhaust hoods run full, the dishwasher cycles, and the HVAC ramps to full cooling, all in the same 15 minutes. That single spike sets the demand charge for the whole month.

$728Monthly demand charge from a 52 kW peak
$532Same total energy, but a 38 kW peak

Identical electricity used. A $196 per month difference, driven entirely by the worst 15 minutes. Over a year, that is roughly $2,350 decided by a few peak moments.

Your Meter

Demand Charge Calculator

See what your peak is costing, and what shaving it would save. Set your building's peak demand and how much you could trim it with smarter operation. The gauge shows your peak; the numbers show the money.

Your peak demand300 kW
Peak reduction with smarter control25%
Demand rate (Oncor commercial)$14 / kW
Demand charge today$4,200 / mo
Demand charge after shaving$3,150 / mo
Annual savings$12,600 / yr
$4,200 demand charge / month
Current peak After shaving

Estimate at Oncor's approximate $14/kW commercial demand rate. Your rate class, TDU territory, and 4CP exposure change the exact figure. Demand reductions of 15 to 40% are commonly achieved through load management.

The 4CP Trap

One Hour a Year That Bills You for Twelve Months

There is a second, sneakier demand charge unique to the Texas grid: the Four Coincident Peak, or 4CP. ERCOT looks at the four 15-minute windows when the entire state grid hit its highest demand, one each in June, July, August, and September. Your building's draw during those four windows sets your transmission charges for the next twelve months.

Add it up and it is remarkable. Four windows, fifteen minutes each, is one single hour. Out of 8,760 hours in a year, your usage during 0.01 percent of them can drive a huge share of your annual transmission cost.

The whole year, and the hour that matters
JanAprJunAugSepDec
60 minutesTotal 4CP window across the entire year, out of 8,760 hours
30%+Share of power cost that 4CP can drive for large facilities

The four amber marks are the only intervals that set 4CP transmission charges. They land on the hottest weekday afternoons of summer, and ERCOT does not announce them in advance.

The catch, and the opportunity, is that those peak windows almost always land on scorching summer afternoons between 3 and 6 p.m., when air conditioning across the state is running flat out. Which points to the real lever hiding underneath every number in this article.

The Real Lever

Why HVAC Controls What You Really Pay

Every hidden layer of a commercial power bill traces back to the same place. HVAC is roughly 39 percent of a building's total energy use, so it is the single largest driver of your kilowatt-hours. But it is also the biggest driver of your peak. When a DFW building's cooling ramps to maximum on a 105-degree afternoon, that is precisely the spike that sets your monthly demand charge and your 4CP exposure.

That is why HVAC is the highest-leverage place to attack the bill. As we covered in how Texas heat breaks commercial HVAC, cooling load peaks exactly when energy is most expensive. Control that load intelligently and you cut kilowatt-hours, demand charges, and 4CP at the same time.

The tools are proven. Building automation can pre-cool a building before the 3 to 6 p.m. peak window, stagger equipment startups so they never all spike at once, and trim setpoints precisely during grid-stress hours. A well-tuned system from consistent preventive maintenance uses less energy for the same comfort. Together they attack every layer of the bill that switching providers never touches.

Common Questions

Texas Commercial Energy FAQ

Because the advertised per-kWh rate is only part of the bill. A commercial bill also carries regulated delivery charges (35 to 45%), demand charges based on your peak 15-minute usage (which can reach 30 to 50%), 4CP transmission charges, and taxes and riders. Texas energy rates really are among the lowest in the country, but those other layers arrive no matter which provider you choose.

A demand charge is billed on the single highest 15-minute burst of power your building draws in a billing period, not your total usage. Your utility multiplies that peak, measured in kilowatts, by a per-kW rate, about $14/kW in Oncor territory. Two buildings with identical total usage pay different demand charges if one draws power in sharp spikes and the other stays steady.

4CP, or Four Coincident Peak, is how ERCOT allocates transmission cost in Texas. It looks at the four 15-minute windows when the whole state grid peaked, one per summer month, and your draw during those windows sets your transmission charges for the next 12 months. For large facilities, that single hour of the year can drive 30 percent or more of power cost. Those windows almost always fall on hot summer afternoons when air conditioning is maxed out.

HVAC is about 39% of a building's energy use, and on hot afternoons it is the biggest single load spiking your demand. Since demand and 4CP charges are set by your peak, the moment your cooling ramps to full is often the exact moment that sets an expensive charge for the whole month or year. Controlling cooling load with automation and maintenance cuts kilowatt-hours and peaks together.

Yes, and unlike delivery charges, they are directly controllable. Pre-cooling before the afternoon peak, staggering equipment startups, improving efficiency, and load management routinely cut peak demand 15 to 40 percent. Since the charge scales with your peak, a 30 percent peak reduction is roughly a 30 percent cut in demand charges. Our building automation team builds exactly these strategies.

Stop Overpaying for Power You Can Control

Kahn Mechanical helps Dallas-Fort Worth buildings cut the load that drives their bill, with smart controls and efficient systems built for the Texas grid. Since 1974.

Sources & References